| Technical data |
| CPU Module |
| Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
| Display |
| Type | I/O LED Indicator |
| Isolation |
| Intra-module Isolation | 2500 VDC |
| EMS Protection |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±8 kV Contact for each Terminal |
| LED Indicators |
| Status | 1 x Power and Communication 4 x Analog Input 4 x Digital Input 4 x Digital Output |
| Analog Output |
| Channels | 4 |
| Type | Voltage Current |
| Range | 0 ~+5 VDC, ±5 VDC, 0 ~ +10 VDC, ±10 VDC, 0 ~ +20 mA, +4 ~ +20 mA |
| Resolution | 16-bit |
| Accuracy | ±0.02%% of FSR |
| Short Circuit Protection | Yes |
| DA Output Response Time | 10 ms per channel |
| Programmable Output Slope | Voltage: 0.0625 ~ 512 V/Second Current: 0.125 ~ 1024 mA/Second |
| Current Output Wiring | Source |
| Open Wire Detection | Yes, for 4 ~ 20 mA only |
| Current Load Resistance | 1000 O |
| Power-on Value | Yes, Programmable |
| Safe Value | Yes, Programmable |
| Digital Input/Counter |
| Channels | 4 |
| Type | Dry Contact Wet Contact |
| ON Voltage Level | Dry: Close to GND Wet: +1 VDC Max. |
| OFF Voltage Level | Dry: Open Wet: +4 ~ 30 VDC |
| Max. Counts | 16-bit (65535) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Effective Distance | 500 M Max. |
| Overvoltage Protection | +60 VDC |
| Digital Output |
| Channels | 4 |
| Type | Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +3.5 VDC ~ +50 VDC |
| Load Current | 700 mA/Channel |
| Overvoltage Protection | 60 VDC |
| Overload Protection | 1.4 A (with short-circuit protection) |
| Short-circuit Protection | Yes |
| Power on Value | Yes, Programmable |
| Safe Value | Yes, Programmable |
| COM Ports |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 4.5 W |
| Mechanical |
| Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
| Installation | DIN-Rail |
| Environmental |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |