| TECHNICAL SPECIFICATIONS |
| Analog Input |
| Input Channels | 5 Differential |
| Type | +/- 20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Resolution | Normal Mode 14-bit |
| Fast Mode | 12-bit |
| Sampling Rate Normal | Mode 10 Hz total |
| Fast Mode | 200 Hz total |
| Accuracy | Normal Mode +/-0.1% |
| Fast Mode | +/-0.5% |
| Zero Drift | +/- 20 µV/°C |
| Span Drift | +/- 25 ppm/°C |
| Input Impedance | 125 O |
| Communication |
| Interface | RS-485 |
| Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON, Modbus/RTU, Modbus/ASCII |
| Dual Watchdog | Yes, Module (2.3 seconds), Communication (Programmable) |
| LED Indicators |
| Power | 1 LED as Power Indicator |
| Isolation |
| Intra-module Isolation, Field-to-Logic | 2500 VDC |
| EMS Protection |
| ESD | (IEC 61000-4-2) +/-4 kV Contact for Each Terminal +/-8 kV Air for Random Point |
| EFT | (IEC 61000-4-4) +/-4 kV for Power |
| Surge | (IEC 61000-4-5) +/-3 kV for Power |
| Power Requirements |
| Reverse Polarity Protection | Yes |
| Powered from Terminal Block | Yes, 10 ~ 30 VDC |
| Consumption | 1 W Max. |
| Mechanical |
| Dimensions (W x L x H) | 52 mm x 98 mm x 27 mm |
| Installation | DIN-Rail Mounting |
| Environment |
| Operating Temperature | -25°C ~ +75°C |
| Storage Temperature | -30°C ~ +75°C |