Specifications |
Isolation | Intra-module Isolation | 2500 VDC |
EMS Protection |
EFT (IEC 61000-4-4) | 4 kV for Power Line |
ESD (IEC 61000-4-2) | 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point |
LED Indicators |
Status | 1 x Power and Communication - 4 x Relay Output |
ZigBee |
Antenna | 2.4 GHz, 5 dBi Omni directional |
Max. Slaves | 255 |
Standard | ZigBee 2007 Pro |
Transmission Power | 11 dBm (Default, FCC Certificated); Max. 19 dBm |
Transmission Range | 700 m (Typical) |
Digital Input |
Channels | 6 |
Type | Isolated, Wet Contact (Sink/Source) |
Wet Contact, ON Voltage Level | +3.5 VDC ~ +30 VDC |
Wet Contact, OFF Voltage Level | Max. +1 VDC |
Input Impedance | 3 kO, 0.33 W |
Digital Output |
Type | Power Relay, Form A |
Relay Output |
Channels | 4 |
Contact Rating | 5 A @ (250 VAC/30 VDC) |
Release Time | Max. 5 ms at Rated Voltage |
Electrical Endurance | Resistive Load: 100,000 ops. min. (10 ops/minute) |
Mechanical Endurance | At No Load: 20,000,000 ops. min. (300 ops/minute) |
Surge Strength | 5,080 V (1.2 / 50us) |
Power |
Input Range | +10 VDC ~ +30 VDC |
Consumption | Max. 1.4 W |
Mechanical |
Dimensions (mm) | 33 x 94 x 110 (W x L x H) |
Installation | DIN-Rail |
Environmental |
Operating Temperature | -25°C ~ +75°C |
Storage Temperature | -30°C ~ +80°C |
Humidity | 10 ~ 90% RH (non-condensing) |