Specifications |
General Data |
Power supply | 10..40 Vdc / 19..28 Vac / 50-60 Hz |
Power Consumption | 2,5 W |
Isolation | 1.500 Vac (3 way) |
Power Transducers | yes |
Status Indicators | Power supply, error, data transmission, data reception, input status |
Protection Degree | IP20 |
THERMOMECHANICAL FEATURES |
Operating Temperature | -10..+60°C |
Dimension | 17.5 x 100 x 112 mm |
Accuracy | 0,1% |
Response time | 35 ms (11 bit)..140 ms (16 bit) |
Setting | Dip- switches EASY_Z109 (PC software) Test-3 (hand held calibrator |
Mounting | 35 mm DIN rail guide |
Input |
Channel Numbers | 1 |
Voltage | (mV, V) Bipolar from 75 mV to 20 V Resolution 15 bit + sign |
Current | Bipolar up to 20 mA Resolution 1 µA |
Rtd | Pt100, Pt500, Pt1000, Ni100, KTY81,KTY84, NTC Measure 3, 4 wires Range: -200..600 °C Resolution 0,1°C |
Thermocouple | Type J, K, R, S, T, E, B, N Resolution 2,5 µV |
Potentiometer | 500 O ..10 kO |
Rheostat | 500 O..25 kO |
Strobe | Alternative to the relay output |
Output |
Channels | 1 |
Voltage | 4 scales: 0..1, 0..5, 0..10, 2..10 V Min load resistance: 2.000 O |
Current | 2 scales: 0/4..20 mA (active/passive) Max load resistance: 600 O |
Relay | Alternative to the strobe NC / NA in case of alarm |
Standard |
Approval | CE, UL-CSA |
Norms | EN 50081-2; EN 55011; EN 50082-2; EN 61000-2-2/4; EN 50140/141; EN 61010-1 |