TECHNICAL SPECIFICATIONS |
General Data |
Power supply | 10..40 Vdc, 19..28 Vac 50..60 Hz |
Power consumption | 2,5 W |
Isolation | 1.500 Vac (3 way) |
Power transducers | Power Supply Error Data Transmission Data Receiving |
Protection Degree | IP20 |
THERMOMECHANICAL FEATURES |
Operating Temperature | -10..+65 °C |
Housing | Nylon 6 with 30% glass-fiber, V0 self-extinguished class |
Connections | Removable terminals block, plug in connectors, max wire size 2.5 mm2 Rear IDC10 connector for Z-PC backplane |
Mounting | 35 mm DIN rail guide 46277 |
COMMUNICATION, PROCESSING, MEMORY |
Interfaces | 2 wires RS485 |
Speed | Up to 115 kbps |
Protocol | ModBUS RTU slave |
Communication Time | < 10 ms (@ 38400 baud) |
Distance | Up to 1200 m |
Connectivity | Max 32 nodes |
Data Memory | EEPROM for the configuration parameters, retention time 40 years |
SIGNALS, MEASUREMENT; CONFIGURATIONS, NORMS |
Channel | 1 input, 1 output |
Type | INPUT N.1 analog channel for load cell (and power supply) up to 4 (350O) or 8 (1.000 O) strain gauge load cells, connection to 4 or 6 wires, impedance equal to 87 O OUTPUT N.1 analog retransmission channel of the net weight in current (0..20, 4..20 mA) or in voltage (0..5, 0..10 V) N.1 Digital Input or Output for calibration tare or weight limit Sensibility: from 1 to 64 mV/V |
Resolution | 24 bit |
Accuracy | 0,01% |
Thermal Drift | 25 ppm/K |
Programming | Z-NET4 (IEC 61131software) EASY SETUP (plug&play software) DIP switches |
Norms & Approvals | CE, EN 61000-6-4/2002, EN 61000-6-2/2002, EN 61010, EN 60742, IEC 61131 |