Specifications |
Digital Input |
Input Channels | 16 |
Input Type | Wet Contact (Sink, Source) |
On Voltage Level | +10 VDC ~ +50 VDC |
Off Voltage Level | +4 VDC Max |
Input Impedance | 10 kO |
Counters | Max. Count | 65535 (16 bits) | Max. Input Frequency | 50 Hz |
Min. Pulse Width | 10 ms |
Over Voltage Protection | +70 VDC |
System |
CPU | 80186 CPU (80 MHz) |
SRAM | 512 KB |
Flash Memory | 512 KB |
EEPROM | 16 KB |
Watchdog | Yes |
Communication |
PoE Ethernet Port | 10/100 Base-TX (With Link, Activity LED Indicator) and automatic MDI/MDI-X |
2-way Isolation |
I/O | 3000 VDC |
Ethernet | 1500 VDC |
EMS Protection |
ESD (IEC 61000-4-2) | 4 kV Contact for each terminal |
EFT (IEC 61000-4-4) | +/-2 kV for Power |
LED Indicators |
PoE | PoE On |
L1 | System Running |
L2 | Ethernet Link/Act |
L3 | Ethernet 10/100M Speed |
Power Requirements |
Required Supply Voltage | Powered by Power-over-Ethernet (PoE) or auxiliary power +12 ~ +48 VDC (non-regulated) |
Powered from PoE | Yes, IEEE 802.3af, Class1 |
Power Consumption | 0.12 A @ 24 VDC Max. |
LED Indicator | Yes |
Mechanical |
Dimensions (W x H x D) | 123 mm x 72 mm x 35 mm |
Installation | DIN-Rail or Wall mounting |
Environment |
Operating Temperature | -25°C ~ +75 °C |
Storage Temperature | -30°C ~ +80 °C |
Relative Humidity | 5 ~ 90% RH, non-condensing |
Software Specifications |
Functions |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators | 3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions. |
12 Emails | Send Email messages to pre-set Email receivers. |
Modbus/ TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions |
DI Channel | ON, OFF, ON to OFF, OFF to ON, Change |
Internal Register | =, >, <, >=, <=(value) |
DI Counter | =, >, <, >=, <=(value), Change |
Timer | Timeout, Not Timeout. |
THEN / ELSE Actions |
DO Channel | ON, OFF, Pulse Output |
Internal Register | Change the value |
DI Counter | Reset |
Timer | Start, Stop |
Email | Send |