| Specifications |
| Analog Input |
| Input Channels | 10 (Differential) |
| Input Type | +/-15 mV, +/-50 mV, +/-100 mV, +/-500 mV,+/-1 V, +/-2.5 V |
| +/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Requires Optional External 125 O Resistor) |
| Thermocouple (J, K, T, E, R, S, B, N,C, L, M, LDIN43710) |
| Resolution | 16-bit |
| Sampling Rate | 10 Samples/Sec. (Total) |
| Accuracy | +/-0.1% |
| Bandwidth | 15.7 Hz |
| Zero Drift | +/-0.5 µV/°C |
| Span Drift | +/-25 µV/°C |
| Input Impedence | >300 kO |
| Common Mode Rejection | 150 dB Min |
| Normal Mode Rejection | 100 dB |
| Overvoltage Protection | 240 Vrms |
| Open Thermocouple Detection | Yes |
| Individual Channel Configuration | Yes |
| ESD Protection | +/-4 kV (Contact for each channel) |
| +/-8 kV air for random point |
| EFT Protection | +/-4 kV for Power |
| Digital Output |
| Output Channels | 6 (Sink) |
| Output Type | Isolated Open Collector |
| Max. Load Current | 700 mA/Channel |
| Load Voltage | 5 VDC ~ 50 VDC |
| System |
| CPU | 80186 CPU (80 MHz) |
| SRAM | 512 KB KB |
| Flash Memory | 512 KB |
| EEPROM | 16 KB |
| Dual Watchdog | Yes |
| Communication |
| PoE Ethernet Port | 10/100 Base-TX (With Link, Activity LED Indicator) and automatic MDI/MDI-X |
| 2 Way Isolaiton |
| Ethernet | 1500 Vrms |
| AI and DO | 2500 Vrms |
| LED Indicators |
| PoE | PoE On |
| L1 | Run |
| L2 | Link/Act |
| L3 | 10/100M |
| Power Requirements |
| IEEE 802.3af | Class 1 |
| Required Supply Voltage | Powered by Power over Ethernet (PoE) or auxiliary power +12 VDC ~ +48 VDC (non-regulated) |
| LED Indicator | Yes |
| Power Consumption | 0.12 A @ 24 VDC Max. |
| Mechanical |
| Dimensions (W x H x D) | 72 mm x 123 mm x 35 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment |
| Operating Temperature | -25°C ~ +75°C |
| Storage Temperature | -30°C ~ +80°C |
| Ambient Relative Humidity | 5 to 90% RH, non-condensing |
| Software Specifications |
| Functions |
| 36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators |
| 3 THEN actions |
| 3 ELSE actions |
| 48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
| 12 Timers | Delay / Timing functions. |
| 12 Emails | Send Email messages to pre-set Email receivers. |
| Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
| Modbus/ TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
| IF Conditions |
| AI Channel | =, >, <, >=, <=(value) |
| Internal Register |
| DO Counter | =, >, <, >=, <=(value), Change |
| Timer | Timeout, Not Timeout. |
| THEN / ELSE Actions |
| DO Channel | ON, OFF, Pulse Output |
| Internal Register | Change the value |
| DO Counter | Reset |
| Timer | Start, Stop |
| Email | Send |