| Specifications |
| Analog Input |
| Input Channels | 7 (Differential) |
| Sensor Type | Pt100, Pt1000, Ni120, Cu100, Cu1000 |
| Wire Connection | 2/3 wire |
| Resolution | 16-bit |
| Sampling Rate | 12 Samples/Sec. (Total) |
| Accuracy | +/-0.05% |
| Zero Drift | +/-0.5 µV/°C |
| Span Drift | +/-20 µV/°C |
| Common Mode Rejection | 150 dB |
| Normal Mode Rejection | 100 dB |
| Input Impedence | > 1M O |
| Open Wire Detection | Yes |
| Individual Channel Configuration | Yes |
| 3-wire RTD Lead Resistance Elimination | Yes |
| System |
| CPU | 16-bit CPU |
| SRAM | 512 KB KB |
| Flash Memory | 512 KB |
| EEPROM | 16 KB |
| Watchdog | Yes |
| Communication |
| PoE Ethernet Port | 10/100 Base-TX and automatic MDI/MDI-X |
| 2 Way Isolaiton |
| I/O | 2500 Vrms |
| EMS Protection |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each terminal and ±8 kV Air for random point |
| EFT (IEC 6000-4-4) | ±4 kV for Power Line |
| LED Indicators |
| PoE | PoE On |
| L1 | System Running |
| L2 | Ethernet Link/Act |
| L3 | Ethernet 10/100M Speed |
| Power Requirements |
| Reserve Polarity Protection | Yes |
| Powered from terminal block | Yes, 12 ~ 48 VDC |
| Powered from PoE | Yes, IEEE 802.3af, Class 1 |
| Consumption | 2.6 W |
| Mechanical |
| Dimensions (W x H x D) | 72 mm x 123 mm x 35 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment |
| Operating Temperature | -25°C ~ +75°C (-13°F ~ +167°F) |
| Storage Temperature | -30°C ~ +80°C (-22°F ~ +176°F) |
| Ambient Relative Humidity | 5 to 90% RH, non-condensing |
| Software Specifications |
| Functions |
| Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
| 36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators |
| 3 THEN actions and 3 ELSE actions |
| 48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
| 12 Timers | Delay / Timing functions. |
| 12 Emails | Send Email messages to pre-set Email receivers. |
| 12 CGI Commands | Send pre-set CGI commands. |
| 12 Recipes | Set up THEN/ELSE action groups. |
| 8 P2P Remote | Set up the connection information for the remote WISE modules. |
| Modbus/ TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
| IF Conditions |
| AI Channel | =, >, <, >=, <=(value) |
| Internal Register |
| Timer | Timeout, Not Timeout. |
| P2P | DI, AI, DI counter, IR |
| Rule Status | Enable, Disable |
| THEN / ELSE Actions |
| Internal Register | Change the value |
| Timer | Start, Stop |
| Email | Send |
| CGI Commands |
| Recipe | Execute |
| P2P | DO (On/Off), AO, IR |
| Rule Status | Enable, Disable |