| Technical Specifications |
| GENERAL DATA |
| Power Supply | Loop powered (5..28 Vdc) |
| Power Consumtption | << 21 mA |
| Isolation/Protection | 3 kVdc (on bare conductors) |
| LED Status Indicators | - |
| Overvoltage category | 300 V CAT III (bare conductor) 600 V CAT III (isolated conductor) |
| Measurement polarity | Positive (incoming current on label side) |
| Protection degree | IP20 |
| Accuracy class | AC: 0,2% f.s. |
| Settings | DIP switch |
| Log Data | - |
| Operating temperature | 20..+65°C |
| Storage temperature | 40..+85°C |
| Humidity | 10rH..90% non condensing |
| Altitude | Up to 2.000 m.a.s.l. |
| Connections | Removable terminals (5 poles), pitch 5 mm for cable up to 2,5 mm2 |
| Max diameter conductor | 12,3 mm |
| Dimension (wxhxd) | 41x44x26 mm |
| Mounting | Free or on DIN rail IEC EN 60715 (35 mm) with accessories |
| Case | PA6, black |
| Weight | 47 g |
| INPUT DATA |
| Channels | 1 |
| Range | 5, 10, 15, 20, 25, 30, 35, 40 A |
| Measurement type | Average adjusted |
| Bipolar measurement | No |
| Hysteresis | - |
| Max instantaneous overcurrent | 800 A |
| Bandwidth/frequency | 20..1.000 Hz |
| Crest factor | 2 |
| OUTPUT DATA |
| Channels | 1 |
| Range | 4..20 mA (2 fili) |
| Resolution | Unlimited |
| Max load | < 5000 Ohm @ 100 Vdc |
| EMI Error | < 40µA |
| Thermal drift | < 150 ppm/K |
| Response time | 100 ms (without filter) 2,5 s (with filter) |
| STANDARD |
| Approvals | CE, UL-UR |
| Norms | EN60688 EN61000-6-4 EN61000-6-2 EN61010-1 |