| Technical specifications |
| GENERAL DATA |
| Power Supply | 10..28 Vdc |
| Power Consumtption | < 25 mA |
| Isolation / Protection | 3 kVdc (on bare conductors) |
| LED Status Indicators | Power Supply / RS485 commmunication |
| Overvoltage category | 300 V CAT III (bare conductor) 600 V CAT III (isolated conductor) |
| Measurement polarity | Positive (incoming current on label side) |
| Protection degree | IP20 |
| Accuracy class | 0,3% f.s. (DC bipolar, AC TRMS) |
| Settings | DIP switch, Software (EASY SETUP) |
| Log Data | Sì |
| Operating temperature | 20..+70°C |
| Storage temperature | 40..+85°C |
| Humidity | 10rH..90% non condensing |
| Altitude | Up to 2.000 m.a.s.l. |
| Connections | Removable terminals (5 poles), pitch 5 mm for cable up to 2,5 mm2 |
| Max diameter conductor | 20,8 mm |
| Dimension (wxhxd) | 95x68x26 mm |
| Mounting | Free or on DIN rail IEC EN 60715 (35 mm) with accessories |
| Case | PA6, black |
| Weight | 120 g |
| COMMUNICATION |
| Communcation port | RS485 |
| Protocol | ModBUS RTU slave |
| Speed | 1.200..115200 bps |
| INPUT DATA |
| Channels | 1 |
| Range | 0..25, 0..50 Aac/dc TRMS ±25 A, ±50 Adc bipolar |
| Measurement type | AC/DC TRMS or DC Bipolar |
| Bipolar measurement | Yes |
| Hysteresis | 0,3% f.s |
| Max instantaneous overcurrent | 300 A (direct) 2.000 A (impulsive) |
| Bandwidth/frequency | 1 kHz |
| Crest factor | 2 |
| OUTPUT DATA |
| Channels | 1 |
| Range | 0..10 V |
| Resolution | 13 bit (10.000 points) |
| Max load | > 2 kOhm |
| EMI Error | < 0,5% |
| Thermal drift | < 200 ppm/K |
| Response time | Fast filter: 800 ms Slow filter: 2 s |
| STANDARD |
| Approvals | CE |
| Norms | EN61000-6-4 EN61000-6-2 EN61010-1 |