| Technical data |
| System |
| Power Supply | Loop powered (9..28 Vdc) |
| Power Consumtption | << 22 mA |
| Isolation/Protection | 3 kVdc (on bare conductors) |
| LED Status Indicators | - |
| Overvoltage category | 300 V CAT III (bare conductor) 600 V CAT III (isolated conductor) |
| Measurement polarity | Positive (incoming current on label side) |
| Protection degree | IP20 |
| Accuracy class | AC: 0,5% f.s, DC: 1% f.s. |
| Settings | DIP switch, Software (EASY SETUP) |
| Log Data | - |
| Operating temperature | 20..+70°C |
| Storage temperature | 40..+85°C |
| Humidity | 10rH..90% non condensing |
| Altitude | Up to 2.000 m.a.s.l. |
| Connections | Removable terminals (5 poles), pitch 5 mm for cable up to 2,5 mm2 |
| Max diameter conductor | 12,3 mm |
| Dimension (wxhxd) | 41x44x26 mm |
| Mounting | Free or on DIN rail IEC EN 60715 (35 mm) with accessories |
| Case | PA6, black |
| Weight | 47 g |
| INPUT DATA |
| Channels | 1 |
| Range | 0..50 Aac/dc TRMS ±50 Adc bipolar |
| Measurement type | AC/DC TRMS or DC Bipolar |
| Bipolar measurement | Yes |
| Hysteresis | 0,3% f.s |
| Max instantaneous overcurrent | 300 A (direct) 2.000 A (impulsive) |
| Bandwidth/frequency | 1 kHz |
| Crest factor | 1,3 |
| OUTPUT DATA |
| Channels | 1 |
| Range | 4..20 mA rated value 3,6 mA fault 22 mA max |
| Resolution | 12 bit |
| Max load | < 1.000 Ohm @ 28 Vdc |
| EMI Error | < 1% |
| Thermal drift | < 200 ppm/K |
| Response time | Fast filter: 500 ms Slow filter: 1 s |
| STANDARD |
| Approvals | CE, UL-UR |
| Norms | EN 61326, EN 61010-1 |