GENERAL SPECIFICATIONS |
GENERAL DATA |
POWER SUPPLY | 8..30 Vdc (stardard battery pack and extended battery packs are optional) |
POWER CONSUMPTION | 3 mW (medium) |
DURATION OF ELECTRICAL AUTONOMY | 3 years |
CONNECTIONS | DB9-Female connector: interface V.24 RS232 SMA Connector: for external antennas I/O's connectors: M6 removable terminals |
MODEM | GSM/GPRS Quad band |
FEATURES | I/O's acquisition and datalogging Transmission Data connection / SMS Dedicated Functions Automatic daily data sent |
COMMUNICATION PORTS | 1 UART GSM port 1 V24-RS232 serial port, half-duplex, local link, settable speed: 1.200.. 115.200 baud rate |
SUPPORTED PROTOCOLS | ModBUS RTU, FTP client, SMS |
DIGITAL INPUT | N° 4 channels galvanically insulated 1.500 Vac, channel sampling freq. 1 Hz; 4 totalizers |
ANALOG INPUT | N° 2 channels with protecntions against surges Range: ±2 V, ±20 V, ±50 V, ±20 mA Resolution 15 bit + sign Accuracy: 0,1% |
DIGITAL OUTPUT | N° 2 relays channels bistables relays with range: 30 Vdc – 1 A max (resistive load) |
PROGRAMMING TOOLS | Software RTU-LP SMS |
PROTECTION DEGREE | IP40 (IP65 optional) |
OPERATING TEMPERATURE | -20..+70 °C (best stability range: 0..35 °C) |
DIMENSIONS WXHXD | 130x65x55 mm |
STANDARDS | CE |