| Technical data |
| Specifications |
| Built-in Web Server | Yes |
| CPU Module |
| Watchdog Timer | Yes, Module (0.8 second), Communication (Programmable) |
| EMS Protection |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators |
| Status | 1 x Power, 2 x Ethernet, 1 x PoE |
| Digital Input/Counter |
| Channels | 12 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Sink/Source |
| ON Voltage Level | +10 VDC ~ +50 VDC |
| OFF Voltage Level | +4 VDC Max. |
| Max. Counts | 4,294,967,285 (32 bits) |
| Frequency | 500 Hz |
| Min. Pulse Width | 1 ms |
| Input Impedance | 10 KO |
| Overvoltage Protection | +70 VDC |
| Digital Output |
| Channels | 6 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +5 VDC ~ +30 VDC |
| Load Current | 100 mA/channel at 25°C Direct Drive Power Relay Module |
| Overvoltage Protection | 60 VDC |
| Overload Protection | 1.3 A |
| Short-circuit Protection | Yes |
| Power on Value | Yes, Programmable |
| Safe Value | Yes, Programmable |
| Ethernet |
| Ports | 1 x RJ-45, 10/100 Base-TX |
| PoE | Yes |
| Security | ID, Password and IP Filter |
| Protocol | Modbus/TCP, Modbus/UDP |
| Power |
| Reverse Polarity Protection | Yes |
| Consumption | 2.4 W |
| Powered from PoE | Yes, IEEE 802.3af, Class1 |
| Powered from Terminal Block | 12 ~ 48 VDC |
| Mechanical |
| Dimensions (mm) | 72 mm x 123 mm x 35 mm (W x L x H) |
| Installation | DIN-Rail or Wall mounting |
| Environmental |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -30 ~ +80°C |
| Humidity | 10 ~ 90% RH, Non-condensing |