| Technical specifications |
| Analog Input |
| Channel | 8 |
| Wiring | 5-channel differential and 3-channel single-ended |
| Input Range | +/-150 mV, +/-500 mV, +/-1 V , +/-5 V, +/-10 V +/-20 mA , 0~20 mA, 4~20 mA (Jumper selectable) |
| Resolution | 12/16-bit |
| Accuracy | Normal Mode: 0.1% Fast Mode: 0.5% |
| Sampling Rate | Normal Mode: 10Hz Fast Mode: 60Hz |
| Input Impedance | Voltage: 20 M (Differential) Currnet: 10 M (Single-ended) |
| Common Voltage Protection | +/-15 VDC |
| Individual Channel Configuration | - |
| Overvoltage Protection | 120 VDC |
| Relay Output |
| Channel | 4 |
| Type | Power Relay (Form A) |
| Contact Rating | 5 A @ 250 VAC 5 A @ 30 VDC |
| Surge Strength | 3000 VDC |
| Operate Time | 3 ms |
| Release Time | 2 ms |
| Mechanical Endurance | 2 × 107 ops. |
| Electrical Endurance | 105 ops. |
| Power-on Value | Yes |
| Safe Value | Yes |
| Communication |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 ~ 115200bps |
| Protocol | DCON Modbus/RTU |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicator/Display |
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator) |
| I/O LED Indicator | - |
| 7-Segment LED Display | Yes |
| Isolation |
| Intra-Module | Isolation, Field-to-Logic 2500 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) | +/-4 kV |
| EFT (IEC 61000-4-4) | +/-4 kV |
| Surge (IEC 61000-4-5) | +/-3 kV |
| Power |
| Reverse Polarity Protection | Yes |
| Input Voltage Range | 10 ~ 30 VDC |
| Consumption | 1.8 W |
| Mechanical |
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -40 ~ +85°C |
| Humidity | 10 ~ 95% RH, Non-condensing |