Technical data |
General Data |
Power supply |
7..30 Vdc |
Hot swapping |
Yes |
Current consumption |
24 mA |
Power consumption |
<660 mW |
A/D Conversion |
16 bit |
Rejection |
50 o 60 Hz (configurable) |
Settings |
50 o 60 Hz (configurable) |
Filter |
Added for stable reading |
Isolation |
1,5 KVac (3-way) |
Isolation technique |
Digital (optocoupler) |
Data processing |
32 bit floating point |
Enclosure |
PBT |
Weight |
45 g |
Connections |
8 Clamp terminals |
Precision class |
0,10% |
Thermal drift |
<120 ppm/K |
Status Indicators |
Fault,alarm |
Programming |
PC software EASY SETUP / EASY LP (by TTL port and EASY-USB or S117P1 converter) |
Advanced settings |
Start / End of measuring scale 2/3/4 wire RTD connection Measuring filter Normal (4 ..20 mA) or inverted output (20 ..4 mA) Input type selection Cable resistance compensation for 2-wire measurement Setting output value in case of fault Over-range Cold junction compensation |
Protection Degree |
IP20 |
Operating |
Temperature |
-20..+65 °C |
Dimension |
(W x H x ) 6,2 x 93 x 102,5 mm |
Input Data |
Channel Numbers |
1 |
Type |
THERMOCOUPLE J,K,R,S,T,E,B,N,L (EN 60584 RTD (Pt100, Pt500, Pt1000, Ni100, NI120, NI1000, Cu50, Cu100) 2, 3, 4 wires connection Voltage (V) ± 30V, impedance 200 kO Voltage (mV) ±150 mV, impedance 10 MO Current: ±24 mA, impedance 40 O Potentiometer: 500 O..10 KO Resistance: up to 1760 O |
Output Data |
Channel Numbers |
1 |
Type |
Current 4..20mA |
Response time(10-90%) |
140..620ms |
Standard |
Approval |
CE, II 3G Ex nA IIC T4 Gc X, II 3D Ex tc IIIC T135°C Dc X |
Norms |
Safety (EN 61010-1), EMC (EN 61000-6-2, EN 61000-6-4, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN61000-4-5, EN 61000-4-6, EN 61000-4-11), Atex (EN60079-0, EN 60079-15) |