Operating Temperature
|
-10°C – 65°C
|
Storage Temperature
|
-25°C – 80°C
|
Program Control
|
Repetitive operation, Stored Program (ROM mode), Periodic operation
|
Method for Controlling I/O
|
Indirect method, Direct method by instruction,
Scan synchronous batch processing system (I/O refresh)
|
Program Language
|
LD (Ladder Diagram), IL (Instruction List), SFC (Sequential Function Chart),
FB (Function Block), FB Extension
|
Number of Instruction
|
Basic Instruction : 60, Application instruction : 480
|
Data Processing
|
LD
|
0.028 µs/step
|
Floating Point
Arithmetic
|
+, -, x, / : 0.4 µs / Instruction
|
Program Memory
|
7M Byte (Including Upload, Parameter, System)
|
Number of Program Block
|
Max 128, up to 65,530 steps per block (PID)
|
Number of I/O
|
8,192 Points (Max 12,288 Points)
|
Number of I/O Devices
|
Input : 131,072 points,
output : 131,072 points
|
Supporting Program
|
LD
|
Scan, Subroutine, Initialize (COLD),
Initialize (HOT), Periodic interruption
|
Special Configuration
|
Initializing special card, PID control,
Thermistor setting, Loadcell setting,
I/O Input module filter setting
|
Communication
|
User protocol (Serial),
User protocol (Ethernet),
MODBUS TCP/RTU Master/Slave,
Ethernet High-speed link,
CIMON-NET Master/Slave,
DNP3, Public network IP setting,
Fieldbus
|
SFC
|
SFC Program
|
Periodic Interruption
|
Maximum 15, cycle setting (10 – 60,000 ms, Unit :10 ms),
priority setting (0 – 14)
|
Base Expansion
|
Maximum 16, Ring structure redundancy
|
Max. Distance
|
S TYPE (Electricity 100 M)
|
Redundancy
|
Supported
|
RUN mode
|
LOCAL / Remote
(RUN, STOP, PAUSE)
|
Restarting
|
Cold, Hot Restart
|
Self-Diagnosis
|
Monitoring delay of processing, problems of memory, IO, battery, power error
|
Data Preservation Against Power Failure
|
K device and conservation (Latch) in M, L, T, C, S, D device
|
WDT
|
Maximum 5000 ms (Unit: 10 ms)
|
Timer
|
On Delay, Off Delay, Addition, Monostable,
Retriggerable Cycle: Either 10 or 100 ms TC (Current value)/TS (Setting value)
|
Counter
|
UP, DOWN, UP/DOWN, RING COUNTER,
CC (Current value)/CS (Setting value)
No limitation on number of points
Count range : -32,768 – +32,767
|
PID
|
32 Channels, Auto-Tuning
|
Communication Channels
|
USB
|
USB 2.0 Mini-B : For Loader Protocol
|
Serial
|
RS-232C (Maximum 115,200 bps) :
CICON Loader, CIMON-HMI, MODBUS RTU Slave
|
Ethernet
|
For expanded communication :10/100Base -T/TX , -FX
|
Event Log
|
Maximum 100 (Power, Mode, Error)
|
Firmware Upgrade
|
Available
|
Power
|
5 V DC, 220 mA
|
Weight
|
138 g
|
Floating-point Arithmetic
|
Supports instructions for floating-point arithmetic
|
Capacity of Scan Program
|
128k steps
|
Device Memory
|
X
|
8192
|
Y
|
8192
|
M
|
16000
|
K
|
16000
|
L
|
16000
|
F
|
2048
|
T
|
4096
|
C
|
4096
|
S
|
100 states * 100 sets (00.00-99.99)
|
D
|
32000 words
|
Z
|
1024 words
|
Q
|
512 words
|
R
|
16 words
|