Technical data |
General |
Standard |
EN61010-1 EN61010-2-201 EN61131-2 |
Dimensions (W × H × D) |
72x90x62mm |
Weight |
240g |
Mounting |
Top hat rail EN50022, 35mm |
Environmental conditions, Indoor use only |
Operating ambient temperature |
0°C – 55°C |
Relative humidity – non-condensing |
80 % for temp. up to 31 °C, decreasing linearly to 50 % relative humidity at 55 °C |
Pollution Degree |
PD2 |
Altitude |
up to 2000m AMSL |
Vibration (5 = f = 9 Hz) Vibration (9 = f = 150 Hz) |
1,75 mm amplitude sinus 3,5 mm amplitude random 0,5 g acceleration sinus 1,0 g acceleration random |
Transport and Storage |
-20°C – +70°C 10 to 90% no condensation Altitude 3000m AMSL |
Shock response |
15g, 11ms half sinus all 3 axes |
I/O |
Supply voltage |
12V or 24V |
USB (Power for programming only) |
USB-B, 2.0 |
Ethernet |
RJ45, 10/100Mbps |
RS485 (no termination inside) |
250kb |
Inputs, no galvanic insulation Common analog/digital Fixed digital, ext. Interrupt usable |
12 10 2 |
Digital Outputs, no galvanic insulation Relay output |
12 10 |
PIN Header, no Galvanic insulation Logic level Input Logic level Output Communication Internal Power |
12 parallel to terminal Inputs 12 parallel to terminal Outputs SPI, 2xUART, I2C, Reset +3,3V, +5V, ARef, GND |
Terminal capacities |
Relay Output, Power Input Strip length Max. tightening torque |
2,5mm² (24-12AWG) 6-7mm 0,5Nm |
Digital, Analog Input Output Strip length Max. tightening torque |
1,5mm² (30-16AWG) 5-6mm 0,2Nm |
Pin header connector |
2x 26 Pin, Dual row, 2.54 pitch |
Protection |
ESD HBM Class 0 |
Contact discharge: ±4kV Air discharge: ±8kV |
Supply input over current protection |
Internal Fuse 20A (fast) |
Relay Output |
External Fuse required |
Digital Output |
Overload, short circuit, ESD |
Signal Input |
Overvoltage, ESD |
Pin header connector Current +5V, +3,3V |
ESD total 200mA, resettable fuse |